Control Command Table
   

In this Topic Hide

ASCII Format

Raw Format

Word / Parameter Formats

Command Number

Group

Cluster / Router

Subnet / Device

CL / Block / Scene

Block / Scene

Level

Proportion

Proportion Change

Fade Time

 

Notes:

  • See Word / Parameter Formats below the following tables for guidance on Words in raw format and parameters in ASCII format.

  • With regards to Direct Level commands, if you enter a negative value, then the output level will be 0; if you enter a value greater than 100, then the level will be 100.

  • When you send a command, if you have entered an invalid parameter or it has been sent to a device, router or cluster that does not exist, then you will receive an error message describing what is wrong with the command. See Error / Diagnostic Messages.

ASCII Format

Note:

  • In an ASCII string, the parameters are not required to be in the order shown below.

 

Name

Parameters

Recall Scene (Group)     

Command Number 11

Group 1..16383

CL 1 or 0
Block 1..8
Scene 1..16

Fade time 0..6553.5s  

 

Recall Scene ( Device )    

Command Number 12

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

Block 1..8
Scene 1..16

Fade time 0..6553.5s

Direct Level (Group)   

Command Number 13

Group 1..16383

Level

0 ... 100%

Fade time 0..6553.5s

 

Direct Level (Device)  

Command Number 14

Cluster 1..253
Router
1..254

Subnet 1..4
Device 1..255

Level  0..100%

Fade time 0..6553.5s

Direct Proportion (Group)    

Command Number 15

Group 1..16383

 

Proportion -100..100%

Fade time 0..6553.5s

Direct Proportion (Device)   

Command Number 16

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

Proportion -100..100%

Fade time 0..6553.5s

Modify Proportion (Group)

Command Number 17

Group 1..16383

 

Proportion Change -100..100%

Fade time 0..6553.5s

Modify Proportion (Device)  

Command Number 18

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

Proportion Change -100..100%

Fade time 0..6553.5s

Emergency Function Test (Group)  

Command Number 19

Group 1..16383

 

 

 

Emergency Function Test (Device)    

Command Number 20

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

 

 

Emergency Duration Test (Group)  

Command Number 21

Group 1..16383

 

 

 

Emergency Duration Test (Device)

Command Number 22

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

 

 

Stop Emergency Tests (Group)

Command Number 23

Group 1..16383

 

 

 

Stop Emergency Tests (Device)

Command Number 24

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

 

 

Raw Format

Name

Word1
(32 bit)

Command Number

Word 2
(32 bit)

Word 3
(32 bit)

Word 4
(32 bit)

Word 5
(32 bit)

Word 6
(32 bit)

Word 7
(32 bit)

Word 8
(32 bit)

Word 9
(32 bit)

Word 10
(32 bit)

Recall Scene (Group)     

11

Group 1..16383

0

CL (MSBit) 1 or 0
Block 1..8
Scene 1..16

0

0

0

Fade time 0..6553.5s

0

0

Recall Scene ( Device )    

12

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

Block 1..8
Scene 1..16

0

0

0

Fade time 0..6553.5s

0

0

Direct Level (Group)   

13

Group 1..16383

0  

0

0

0

Level  

0..100%

Fade time 0..6553.5s

0

0

Direct Level (Device)   

14

Cluster 1..253
Router
1..254

Subnet 1..4
Device 1..255

0

0

0

Level

0..100%

Fade time 0..6553.5s

0

0

Direct Proportion (Group)    

15

Group 1..16383

 0

0

0

0

Proportion  -100..100%

Fade time 0..6553.5s

0

0

Direct Proportion (Device)   

16

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

0

0

0

Proportion  -100..100%

Fade time 0..6553.5s

0

0

Modify Proportion (Group)

17

Group 1..16383

0

0

0

0

Proportion Change -100..100%
 

Fade time 0..6553.5s

0

0

Modify Proportion (Device)  

18

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

0

0

0

Proportion Change
-100..100%

Fade time 0..6553.5s

0

0

Emergency Function Test (Group)  

19

Group 1..16383

0

0

0

0

0

0

0

0

Emergency Function Test (Device)    

20

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

0

0

0

0

0

0

0

Emergency Duration Test (Group)  

21

Group 1..16383

0

0

0

0

0

0

0

0

Emergency Duration Test (Device)

22

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

0

0

0

0

0

0

0

Stop Emergency Tests (Group)

23

Group 1..16383

0

0

0

0

0

0

0

0

Stop Emergency Tests (Device)

24

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

0

0

0

0

0

0

0

Word / Parameter Formats

Command Number

Raw Format

31..........................24

23.................16

15...................8

7....................0

Message Type [31:24]

Ack[23],
HelvarNet
Version [22:16]

0 0 0 0 0 0 0 0

Command Number [7:0]

Byte 3

Byte 2

Byte 1

Byte 0

 

ASCII Format

Command Number = 11..25 (in control commands' case)

Group

Raw Format

31.................24

23.................16

15...................8

7....................0

0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0

0

Group [14:0]

Byte 3

Byte 2

Byte 1

Byte 0

ASCII Format

Group = 1..16383

Cluster / Router

Raw Format

31.................24

23.................16

15...................8

7....................0

0 0 0 0 0 0 0 0

Cluster [23:16]

0 0 0 0 0 0 0 0

Router [7:0]

Byte 3

Byte 2

Byte 1

Byte 0

ASCII Format

Cluster = 1..253, Router = 1..254

Subnet / Device

Raw Format

31.................24

23.................16

15...................8

7....................0

0 0 0 0 0 0 0 0

0 0 0 0 0

Subnet [18:16]

0 0 0 0 0 0 0 0

Device [7:0]

Byte 3

Byte 2

Byte 1

Byte 0

ASCII Format

Subnet = 1..4, Device = 1..255

CL / Block / Scene

If you want to call a constant light scene, then send the CL flag (a value of 1).

Note:

  • The scene called will only be a constant light scene if configured so in Designer.

Raw Format

31.................24

23.................16

15...................8

7.........................0

CL

0 0 0 0 0 0 0

0 0 0 0

Block [19:16]

0 0 0 0 0 0 0 0

0 0 0

Scene [4:0]

Byte 3

Byte 2

Byte 1

Byte 0

ASCII Format

Constant Light = 1 (True) or 0 (False), Block = 1..8, Scene = 1..16

Note:

  • If any other block / scene values are requested then you will receive an 'Invalid block parameter' or 'Invalid scene parameter' error.

Block / Scene

Raw Format

31.................24

23.................16

15...................8

7.........................0

0 0 0 0 0 0 0 0

0 0 0 0

Block [19:16]

0 0 0 0 0 0 0 0

0 0 0

Scene [4:0]

Byte 3

Byte 2

Byte 1

Byte 0

 

ASCII Format

Block = 1..8, Scene = 1..16

Note:

  • If any other block / scene values are requested then you will receive an 'Invalid block parameter' or 'Invalid scene parameter' error.

Level

Raw Format

31.................24

23.................16

15...................8

7....................0

0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0

0

Level [6:0]

Byte 3

Byte 2

Byte 1

Byte 0

 

ASCII Format

Level = 0..100

Note:

  • If a value greater than 100 is requested then this is rounded down to 100.

  • If a negative value is requested then this is rounded up to 0.

Proportion

Raw Format:

31.................24

23.................16

15...................8

7....................0

0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0

Proportion [7:0]

Byte 3

Byte 2

Byte 1

Byte 0

ASCII Format

Proportion = -100..100

Proportion Change

Raw Format

31.................24

23.................16

15...................8

7....................0

0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0

Proportion Change [7:0]

Byte 3

Byte 2

Byte 1

Byte 0

 

ASCII Format

Proportion Change = -100..100

Fade Time

The fade time is represented as hh:mm:ss:th; where hh represents hours, mm represents minutes, ss represents seconds and th represents tenths (t) and hundredths (h) of seconds.

Note:

  • The maximum fade time for DALI / DIGIDIM devices is 90 seconds; the maximum for Imagine / SDIM-connected devices is 46 hours.

 

Fade Time

ASCII

Hexadecimal

0.01 second

1

0x00000001

0.1 second

10

0x0000000A

1 second

100

0x00000064

60 seconds (1 minute)

6000

0x00001770

60 minutes (1 hour)

360000

0x00057E40

Raw Format

31.................24

23.................16

15...................8

7....................0

0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0

0 0 0

Fade Time [12:0]

Byte 3

Byte 2

Byte 1

Byte 0

 

Related Topics