Query Command Table
   

Note:

  • For guidance on Words in raw format and parameters in ASCII format, see Word / Parameter Formats below table .

  • When you send a command, if you have entered an invalid parameter or it has been sent to a device, router or cluster that does not exist, then you will receive an error message describing what is wrong with the command. For more information, see Error / Diagnostic Messages.

ASCII Format

Note:

  • In an ASCII string, the parameters are not required to be in the order shown below.

 

Name

Parameters

Query Lamp Running Hours

Command Number 70

 

 

 

Query Ballast Running Hours

Command Number 71

 

 

 

Query Maximum Voltage

Command Number 72

 

 

 

Query Minimum Voltage

Command Number 73

 

 

 

Query Maximum Temperature

Command Number 74

 

 

 

Query Minimum Temperature

Command Number 75

 

 

 

Query Clusters

Command Number 101

 

 

 

Query Routers

Command Number 102

Cluster 1..253

 

 

Query LSIB

Command Number 103

Group 1..16383

Block 1..8

 

Query Device Type

Command Number 104

Cluster 1..253
Router
1..254

Subnet 1..4
Device 1..255

 

Query Description Group

Command Number 105

Group 1..16383

 

 

Query Description Device

Command Number 106

Cluster 1..253
Router
1..254

Subnet 1..4
Device 1..255

 

Query Device State  

Command Number 110

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

 

Query Device Is Disabled

Command Number 111

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

 

Query Lamp Failure

Command Number 112

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

 

Query Device Is Faulty

Command Number 113

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

 

Query Device Is Missing

Command Number 114

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

 

Query Emergency Battery Failure

Command Number 129

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

 

Query Measurement

Command Number 150

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

Subdevice 1..16 /
0 (0x0 = no subdevice specified)

Query Inputs

Command Number 151

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

Subdevice 1..16 /
0 (0x0 = no subdevice specified)

Query Load Level

Command Number 152

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

 

Query Power Consumption

Command Number 160

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

 

Query Group Power Consumption

Command Number 161

Group 1..16383

 

 

Query Emergency Function Test Time

Command Number 170

 

 

 

Query Emergency Function Test State

Command Number 171

 

 

 

Query Emergency Duration Test Time

Command Number 172

 

 

 

Query Emergency Duration Test State

Command Number 173

 

 

 

Query Emergency Battery Charge

Command Number 174

 

 

 

Query Emergency Battery Time

Command Number 175

     

Query Emergency Total Lamp Time

Command Number 176

 

 

 

Query Time  

Command Number 185

 

 

 

Query Longitude

Command Number 186

 

 

 

Query Latitude

Command Number 187

 

 

 

Query Time Zone

Command Number 188

 

 

 

Query Daylight Saving Time

Command Number 189

 

 

 

Query Software Version

Command Number 190

 

 

 

Query HelvarNet Version

Command Number 191

 

 

 

Raw Format

Name

Command Number Word1 ((32 bit)

Word 2
(32 bit)

Word 3
(32 bit)

Word 4
(32 bit)

Word 5
(32 bit)

Word 6
(32 bit)

Word 7
(32 bit)

Word 8
(32 bit)

Word 9
(32 bit)

Word 10
(32 bit)

 

Query Lamp Running Hours

70

 

 

 

 

 

 

 

 

 

Query Ballast Running Hours

71

 

 

 

 

 

 

 

 

 

Query Maximum Voltage

72

 

 

 

 

 

 

 

 

 

Query Minimum Voltage

73

 

 

 

 

 

 

 

 

 

Query Maximum Temperature

74

 

 

 

 

 

 

 

 

 

Query Minimum Temperature

75

 

 

 

 

 

 

 

 

 

Query Clusters  

101

0

0

0

0

0

0

0

0

0

Query Routers

102

Cluster 1..253

0

0

0

0

0

0

0

0

Query LSIB

103

Group 1..16383

0

Block 1..8 / 0

0

0

0

0

0

0

Query Device Type

104

 

Cluster 1..253
Router
1..254

Subnet 1..4
Device 1..255

0

0

0

0

0

0

0

Query Description Group

105

Group 1..16383

0

0

0

0

0

0

0

0

Query Description Device

106

Cluster 1..253
Router
1..254

Subnet 1..4
Device 1..255

0

0

0

0

0

0

0

Query Device State   

110

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

0

0

0

0

0

0

0

Query Device Is  Disabled

111

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

0

0

0

0

0

0

0

Query Lamp Failure

112

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

0

0

0

0

0

0

0

Query Device Is Faulty

113

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

0

0

0

0

0

0

0

Query Device Is Missing

114

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

0

0

0

0

0

0

0

Query Emergency Battery Failure

129

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

0

0

0

0

0

0

0

Query Measurement    

150

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

Subdevice 1..16 /

0 (0x0 = no subdevice specified)

0

0

0

0

0

0

Query Inputs    

151

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

Subdevice 1..16 /

0 (0x0 = no subdevice specified)

0

0

0

0

0

0

Query Load Level

152

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

0

0

0

0

0

0

0

Query Power Consumption

160

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

0

0

0

0

0

0

0

Query Group Power Consumption

161

Group 1..16383

0

0

0

0

0

0

0

0

Query Emergency Function Test Time

170

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

0

0

0

0

0

0

0

Query Emergency Function Test State

171

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

0

0

0

0

0

0

0

Query Emergency Duration Test Time

172

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

0

0

0

0

0

0

0

Query Emergency Duration Test State

173

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

0

0

0

0

0

0

0

Query Emergency Battery Charge

174

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

0

0

0

0

0

0

0

Query Emergency Battery Time

175

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

0

0

0

0

0

0

0

Query Emergency Total Lamp Time

176

Cluster 1..253
Router 1..254

Subnet 1..4
Device 1..255

0

0

0

0

0

0

0

Query Time  

185

0

0

0

0

0

0

0

0

0

Query Longitude

186

0

0

0

0

0

0

0

0

0

Query Latitude

187

0

0

0

0

0

0

0

0

0

Query Time Zone

188

0

0

0

0

0

0

0

0

0

Query Daylight Saving Time

189

0

0

0

0

0

0

0

0

0

Query Software Version

190

0

0

0

0

0

0

0

0

0

Query HelvarNet Version

191

0

0

0

0

0

0

0

0

0

Word / Parameter Formats

Note:

Cluster

Raw Format

31.................24

23.................16

15...................8

7....................0

0 0 0 0 0 0 0 0

Cluster [23:16]

0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0

Byte 3

Byte 2

Byte 1

Byte 0

 

ASCII Format

Cluster = 1..253

Block

Raw Format

31.................24

23.....................16

15...................8

7....................0

0 0 0 0 0 0 0 0

0 0 0 0

Block [19:16]

0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0

Byte 3

Byte 2

Byte 1

Byte 0

 

ASCII Format

Block = 1..8

Subdevice

Raw Format

31.................24

23.....................16

15...................8

7....................0

0 0 0 0 0 0 0 0

0 0 0 0

Subevice

[19:16]

0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0

Byte 3

Byte 2

Byte 1

Byte 0

ASCII Format

Subdevice = 1..16

 

Related Topics